Section 360-381-202Equipment Issue 2Fourth Printing, December 2006Telecommunications Group2006 Charles Industries Ltd.All rights reserved. Printed in
Section 360-381-202105.1.2. Installing a New UnitUse the following steps to install the T1-S.Step Action1. If not already installed, install the rear
Section 360-381-20211Table 1. LED DefinitionsLabel Color Status Indicates that...POWER Green ON The unit is receiving power.OFF The unit is not power
Section 360-381-20212Table 3. RJ48 T1 Jack PinoutsPin # Use1 R (RCV from network)123456782 T (RCV from network1 2 3 4 5 6 7 83 —4 R1 (XMT to network)
Section 360-381-202136.2 Software OptioningThis unit comes from the factory with default provisioning, which can be changed through the Network Manage
Section 360-381-20214T1 restore to Red Alarm retired 15 Sec. 1 Sec. 1 Sec.Yellow alarm detected to declared < 1 Sec. < 1 Sec. < 1 Sec.Yellow
Section 360-381-20215Operations Channel (EOC), if the T1 is utilizing EFS format, or can utilize a timeslot in the T1. This is donethrough the optioni
Section 360-381-202162. Include the following information:− Company name and address− Contact name and phone number− Inventory of equipment being ship
Section 360-381-20217Parameter SpecificationT1 connector (rear panel.) RJ48PC control interface:Two types of connectors. (RS232 with RJ11 onthe front
Section 360-381-20221. GENERAL1.1 Document PurposeThis document provides general, installation and testing information for the T1 Controller Unit (T1-
Section 360-381-2023 Temperature hardened (−40 to +65 C) Combines the functions of a LIU and a CSU, allowing direct connections to public T1 network
Section 360-381-2024 Remote terminal status in a CO/RT configuration Tone/pattern test generator and error detection1.9 LoopbacksThe T1-S provides t
Section 360-381-2025face to a powered line that uses line-powered repeaters. See Figure 2 and Figure 3 for typical applications. Otherapplications use
Section 360-381-2026Figure 3 shows a similar application, except the DS1 facility is fractional “T1”. The 360-80 ICB maps the physicalslots into the f
Section 360-381-2027(east). The data/voice on the Primary T1 can be “dropped” to any one of the cards in the 360-80. Any data/voicethat is not “droppe
Section 360-381-2028When a new channel card is installed in the system or a system reset to factory default values is performed, thedefault timeslot a
Section 360-381-2029PrimaryT1Timeslot 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Channel 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17